AL conductor XLPE insulated PVC sheated steel wire armored power cable not only have excellent electric, mechanical properties, but also have powerful resistance against chemical corrosion, heataging and environmental stress. Their structures are simple. The permissible maximum operating temperature is 90'C. It is convenient for using, and they can be laid with no restriction of different elevation.
Type | Name | Main Application | |
Cu Core | Al Core | ||
YJV YJY |
YJLV YJLY |
XLPE insulated,PVC or PE Sheathed Power Cable | For laying indoor,tunnel,channel and undergroud,Unable to bear external mechanical force,but bear the traction force during laid |
YJV22 YJY22 |
YJLV22 YJLY23 |
XLPE Insulated,Steel Tape Armoured,PVC or PE Sheathed Power Cable | For laying indoor,tunnel,channel and undergroud Able to bear external mechanical force,but unable to bear large pulling force |
YJV32 YJY32 |
YJLV32 YJLY32 |
XLPE Insulated,Fine Steel Wire Armoured,PVC or PE Sheathed Power Cable | For laying in shaft with large difference of level.Able to bear external machanical force and maderate pulling force |
YJV42 YJY42 |
YJLV42 YJLY42 |
XLPE Insulated,Thick Steel Wire Armoured,PVC or PE Sheathed Power Cable | Able to bear positive pressure and pulling force |
Reference Standards: | IEC60502-2, IEC 60228, IEC60332 -1/2/3, BS6622, BS7835, VDE0276, AS/NZS 1429.1, GB/T 12706, etc. |
Rated Voltage: | 6/10kV, 6.35/11kV (12kV), 8.7/15kV, 12/20kV, 18/30kV,19/33kV |
Core Number: | Single Core or Three Core (1C or 3C) |
Available Dimensions: | 25mm2, 35mm2, 50mm2, 70mm2, 95mm2, 120mm2, 150mm2, 185mm2, 240mm2, 300mm2, 400mm2, 500mm2, 630mm2. |
Codes Available: | N2XSY, N2XSEY, NA2XSY, NA2XSEY, N2XSRY, NA2XSRY, N2XSEBY, N2XSEYBY, NA2XSEBY, N2XSERY, NA2XSERY, N2XSEYRGbY, NA2XSEYRGbY, N2XS(F)2Y, NA 2XS(F)2Y, N2XS(FL)2Y, N2XSH, N2XSYRY |
YJV, YJLV, YJSV, YJLSV, YJV72, YJLV72, YJSV72, YJLSV72, YJV22, YJLV22, YJLV23,YJSV22, YJLSV22, YJV32, YJLV32, YJSV32, YJLSV32 | |
Application: | For power networks, underground, outdoors and in cable ducting. It is recommended that the installation instructions indicated by the Local Electric Code, or any equivalent, be followed, so that the safeguarding of persons and the integrity of the product will not be affected during installation. |
Construction: | |
Conductor: | Stranded round compacted copper or aluminum conductor (Cu / Al ), copper wire annealed. |
Conductor Screen: | Semi-conducting material |
Insulation: | XLPE (Cross-Linked Polyethylene) |
Insulation Screen: | Semi-conducting material |
Metallic Screen: | Copper tape screen or copper wire screen (CTS / CWS ) |
Filler: | PP rope |
Separator: | Binding tape |
Bedding: | PVC (Polyvinyl Chloride) |
Armouring: | Single Core: Aluminium Wire Armoured (AWA) Multi-core: Steel Wire Armoured (SWA) or Steel Tape Armoured (STA) |
Sheath: | PVC (Polyvinyl Chloride), flame retardant PVC, PE, LSOH, HFFR |
Colour: | Red or Black |
Temperature Rating: | 0°C to 90°C |
Minimum Bending Radius: | Single Core: 15 x overall diameter Three Core: 12 x overall diameter (Single Core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former) |
Cable Voltage Test and Partial Discharge Test
Rate Voltage Uo(kv) |
Item | 0.6/1 | 1.8/3 | 3.6/6 | 6.6/6 6.6/10 |
8.7/10 8.7/15 |
12/20 | 18/20 18/30 |
21/35 | 26/35 |
Voltage | Test Voltage | 3.5 | 6.5 | 12.5 | 21 | 30.5 | 42 | 63 | 73.5 | 91 |
Test Time | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | |
Partial Discharge Test | Test Voltage | _ | _ | 6.2 | 10.4 | 15.1 | 20.8 | 31.1 | 36.3 | 45 |
Discharge Capacity | _ | _ | 10 | 10 | 10 | 10 | 10 | 10 | 10 |