Customization: | Available |
---|---|
Application: | Construction, Underground, Industrial, Power Station, Telecommunication, Distribution Points |
Voltage: | Low and Medium Voltage Cable |
Still deciding? Get samples of US$ 0/Meter
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Application
PVC and FR PVC 70°C cables suitable for wiring in residential and commercial infrastructure.
HR PVC 85°C cables are suitable for wiring in residential and commercial infrastructure for a higher ambient temperature.
FR-LSH cables are suitable for wiring in public places like schools, hospitals, theatres, etc.
Technical Data
Approvals : IS 694 marked, FIA/TAC
Conductor : Electrolytic grade annealed copper Class 5 as per IS 8130
Standard Cable Colour : Black, grey & white
Voltage Rating : Up to and including 1100V
Packing : Standard packing of 100 mtr. in coil. Longer length available on request
Variants Available
Product Type/Legends | Specifications |
---|---|
RATNAFLEX-M | IS 694, IS 8130 Class 5, IS 5831 Type D for insulation & ST-3 & for sheathing |
RATNAFLEX-M HR | IS 694, IS 8130 Class 5, IS 5831 Type C for insulation & ST-2 for sheathing |
RATNAFLEX-M FR | IS 694, IS 8130 Class 5, IS 5831 Type D for insulation & ST-3 (FR) & for sheathing |
RATNAFLEX-M HR FR | IS 694, IS 8130 Class 5, IS 5831 Type C for insulation & ST-2 (FR) for sheathing |
RATNAFLEX-M FR-LSH | IS 694, IS 8130 Class 5, IS 5831 Type D for insulation & ST-3 (FR-LSH) for sheathing |
Please complete the part numbers for these cables by adding the suffix (in place of 'xx') for the insulation colour required. | Kindly complete the part numbers for these cables by adding the suffix (in place of 'y') for the product type required. | Kindly complete the part numbers for these cables by adding the suffix (in place of 'z') for the sheath colour required. |
06 - green-yellow earth core. We offer green/yellow earth core as our standard product. 00 - without green-yellow earth core (available on request). | 1 - PVC 70°C, 2 - PVC FR 70°C, 3 - PVC HR 85°C, 4 - PVC HR 85°C + FR, 5 - PVC FR-LSH. | 1 - black, 4 - grey, 5 - white. |
Cable Design Parameters
No. of Cores | Nominal Cross Sectional Area(Sq. mm) | Nominal Insulation Thickness (mm) | Max. D.C. Conductor Resistance at 20°C(Ω/km) | Nominal Thickness of Sheath | Maximum Overall Dimensions (mm) |
---|---|---|---|---|---|
1 | 0.5 | 0.60 | 39.0 | 0.9 | 4.3 |
2 | 0.5 | 0.60 | 39.0 | 0.9 | 6.9 |
3 | 0.5 | 0.60 | 39.0 | 0.9 | 7.3 |
4 | 0.5 | 0.60 | 39.0 | 0.9 | 8.0 |
5 | 0.5 | 0.60 | 39.0 | 0.9 | 8.7 |
1 | 0.75 | 0.60 | 26.0 | 0.9 | 4.5 |
2 | 0.75 | 0.60 | 26.0 | 0.9 | 7.3 |
3 | 0.75 | 0.60 | 26.0 | 0.9 | 7.7 |
4 | 0.75 | 0.60 | 26.0 | 0.9 | 8.4 |
5 | 0.75 | 0.60 | 26.0 | 0.9 | 9.2 |
1 | 1 | 0.60 | 19.5 | 0.9 | 4.7 |
2 | 1 | 0.60 | 19.5 | 0.9 | 7.6 |
3 | 1 | 0.60 | 19.5 | 0.9 | 8.1 |
4 | 1 | 0.60 | 19.5 | 0.9 | 8.8 |
5 | 1 | 0.60 | 19.5 | 1.0 | 9.6 |
1 | 1.5 | 0.60 | 13.3 | 0.9 | 5.4 |
2 | 1.5 | 0.60 | 13.3 | 0.9 | 8.9 |
3 | 1.5 | 0.60 | 13.3 | 0.9 | 9.4 |
4 | 1.5 | 0.60 | 13.3 | 1.0 | 10.4 |
5 | 1.5 | 0.60 | 13.3 | 1.0 | 11.4 |
1 | 2.5 | 0.70 | 7.98 | 1.0 | 6.2 |
2 | 2.5 | 0.70 | 7.98 | 1.0 | 10.3 |
3 | 2.5 | 0.70 | 7.98 | 1.0 | 10.9 |
4 | 2.5 | 0.70 | 7.98 | 1.0 | 12.0 |
5 | 2.5 | 0.70 | 7.98 | 1.0 | 13.2 |
1 | 4 | 0.80 | 4.95 | 1.0 | 6.8 |
2 | 4 | 0.80 | 4.95 | 1.0 | 11.6 |
3 | 4 | 0.80 | 4.95 | 1.0 | 12.4 |
4 | 4 | 0.80 | 4.95 | 1.0 | 13.6 |
5 | 4 | 0.80 | 4.95 | 1.1 | 15.3 |
1 | 6 | 0.80 | 3.30 | 1.1 | 7.5 |
2 | 6 | 0.80 | 3.30 | 1.1 | 13.0 |
3 | 6 | 0.80 | 3.30 | 1.2 | 13.8 |
4 | 6 | 0.80 | 3.30 | 1.2 | 15.5 |
1 | 10 | 1.00 | 1.91 | 1.3 | 9.4 |
2 | 10 | 1.00 | 1.91 | 1.3 | 16.5 |
3 | 10 | 1.00 | 1.91 | 1.4 | 17.7 |
4 | 10 | 1.00 | 1.91 | 1.4 | 19.5 |
1 | 16 | 1.00 | 1.21 | 1.4 | 10.9 |
2 | 16 | 1.00 | 1.21 | 1.4 | 19.4 |
3 | 16 | 1.00 | 1.21 | 1.4 | 20.6 |
4 | 16 | 1.00 | 1.21 | 1.4 | 23.0 |
1 | 25 | 1.20 | 0.780 | 1.4 | 13.6 |
2 | 25 | 1.20 | 0.780 | 1.4 | 23.8 |
3 | 25 | 1.20 | 0.780 | 1.5 | 25.6 |
4 | 25 | 1.20 | 0.780 | 1.6 | 28.5 |
1 | 35 | 1.20 | 0.554 | 1.6 | 15.5 |
2 | 35 | 1.20 | 0.554 | 1.6 | 27.2 |
3 | 35 | 1.20 | 0.554 | 1.6 | 29.3 |
4 | 35 | 1.20 | 0.554 | 1.7 | 32.7 |
1 | 50 | 1.40 | 0.386 | 2.0 | 18.1 |
2 | 50 | 1.40 | 0.386 | 2.0 | 32.0 |
3 | 50 | 1.40 | 0.386 | 2.0 | 34.6 |
4 | 50 | 1.40 | 0.386 | 2.0 | 38.6 |
1 | 70 | 1.40 | 0.272 | 2.2 | 20.8 |
2 | 70 | 1.40 | 0.272 | 2.2 | 36.8 |
3 | 70 | 1.40 | 0.272 | 2.2 | 39.6 |
4 | 70 | 1.40 | 0.272 | 2.2 | 44.3 |
1 | 95 | 1.60 | 0.206 | 2.4 | 23.6 |
2 | 95 | 1.60 | 0.206 | 2.4 | 41.8 |
3 | 95 | 1.60 | 0.206 | 2.4 | 47.0 |
4 | 95 | 1.60 | 0.206 | 2.4 | 50.2 |
1 | 120 | 1.60 | 0.161 | 2.5 | 26.0 |
2 | 120 | 1.60 | 0.161 | 2.5 | 46.2 |
3 | 120 | 1.60 | 0.161 | 2.5 | 51.0 |
4 | 120 | 1.60 | 0.161 | 2.5 | 55.7 |
3 | 150 | 1.80 | 0.129 | 2.6 | 54.8 |
4 | 150 | 1.80 | 0.129 | 2.6 | 62.1 |
3 | 185 | 2.00 | 0.106 | 2.8 | 61.2 |
4 | 185 | 2.00 | 0.106 | 2.8 | 68.5 |
3 | 240 | 2.20 | 0.0801 | 3.0 | 69.7 |
4 | 240 | 2.20 | 0.0801 | 3.0 | 77.9 |
3 | 300 | 2.40 | 0.0641 | 3.2 | 75.7 |
4 | 300 | 2.40 | 0.0641 | 3.2 | 84.4 |
Usage:
The power cables with copper screening are used mainly in distribution points of high voltage and very high voltage, for connecting in systems where the resistance to interference (EMC) is required, in the circuits of pulsed supply with frequency converters and everywhere that higher requirement against penetration or radiation of interfering signals is demanded. It is possible to use them in dry or wet environment and for placement into the soil.
The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to 60079-11.
Power cable from PVC with copper screening meeting the requirements of EMC
Construction:
1. Conductor Cu conductor of the category 1 or 2 according to IEC 60228
2. Insulation PVC
3. Cable core wrapping by PET foil
4. Bedding PVC
5. Screening double Cu foil wrapped in opposite directions
6. Sheath PVC
Technical parameters:
Rated voltage U0/U: 0,6/1 kV AC
Highest voltage of the Um system: 1,2 kV AC
Testing voltage between cores: 4 kV AC 5 min
Testing voltage between core and screening: 4 kV AC 5 min
Surrounding temperatures (fixed placement): - 30°C up to + 70°C
Surrounding temperatures (during installation): -5°C up to +50°C
Minimum bending radius (fixed placement): 10D
Basic characteristics:
Self-extinguishing PVC: EN 60332-1-2
Colour marking of cores: HD 308 S2
Sheath colour: black
1-CYKFY Power Control Cable Parameter
Cores x Section Area | Insulation Thickness | Jacket Thickness | Maximum resistance at 20ºC | Cable Diameter | Copper approx. weight | Cable Approx. Weight | Packing Length |
mm2 | mm | mm | Ω/km | mm | kg/km | kg/km | m |
7 x 1 | 0.6 | 1.2 | 18.10 | 13.00 | 115 | 270 | 2750 |
12 x 1 | 0.6 | 1.2 | 18.10 | 15.50 | 175 | 400 | 2500 |
19 x 1 | 0.6 | 1.2 | 18.10 | 17.50 | 248 | 520 | 1750 |
2 x 1.5 | 0.7 | 1.2 | 12.10 | 11.00 | 70 | 190 | 2000 |
3 x 1.5 | 0.7 | 1.2 | 12.10 | 11.50 | 86 | 210 | 2000 |
4 x 1.5 | 0.7 | 1.2 | 12.10 | 12.50 | 110 | 250 | 2000 |
5 x 1.5 | 0.7 | 1.2 | 12.10 | 13.50 | 125 | 280 | 2000 |
7 x 1.5 | 0.7 | 1.2 | 12.10 | 4.50 | 153 | 340 | 2000 |
12 x 1.5 | 0.7 | 1.2 | 12.10 | 17.50 | 239 | 510 | 1750 |
14 x 1.5 | 0.7 | 1.4 | 12.10 | 18.50 | 297 | 560 | 1750 |
19 x 1.5 | 0.7 | 1.4 | 12.10 | 21.00 | 347 | 720 | 1250 |
24 x 1.5 | 0.7 | 1.4 | 12.10 | 24.00 | 432 | 1000 | 1000 |
27 x 1.5 | 0.7 | 1.4 | 12.10 | 24.50 | 477 | 1000 | 750 |
37 x 1.5 | 0.7 | 1.4 | 12.10 | 27.50 | 622 | 1250 | 750 |
48 x 1.5 | 0.7 | 1.6 | 12.10 | 31.50 | 750 | 1600 | 500 |
2 x 2.5 | 0.7 | 1.2 | 7.41 | 12.00 | 93 | 220 | 1500 |
3 x 2.5 | 0.7 | 1.2 | 7.41 | 12.50 | 119 | 260 | 1500 |
4 x 2.5 | 0.7 | 1.2 | 7.41 | 13.50 | 146 | 310 | 1500 |
5 x 2.5 | 0.7 | 1.2 | 7.41 | 14.50 | 173 | 350 | 1500 |
7 x 2.5 | 0.7 | 1.2 | 7.41 | 15.50 | 223 | 420 | 1500 |
12 x 2.5 | 0.7 | 1.4 | 7.41 | 20.00 | 358 | 680 | 1500 |
19 x 2.5 | 0.7 | 1.4 | 7.41 | 22.50 | 529 | 930 | 1000 |
24 x 2.5 | 0.7 | 1.4 | 7.41 | 26.50 | 663 | 1310 | 750 |
27 x 2.5 | 0.7 | 1.4 | 7.41 | 27.00 | 680 | 1400 | 750 |
2 x 4 | 0.7 | 1.2 | 4.61 | 13.50 | 125 | 290 | 1000 |
3 x 4 | 0.7 | 1.2 | 4.61 | 14.00 | 165 | 330 | 1000 |
4 x 4 | 0.7 | 1.2 | 4.61 | 15.00 | 206 | 400 | 1000 |
5 x 4 | 0.7 | 1.2 | 4.61 | 16.00 | 247 | 460 | 1000 |
7 x 4 | 0.7 | 1.2 | 4.61 | 17.50 | 325 | 560 | 1000 |
12 x 4 | 0.7 | 1.4 | 4.61 | 22.50 | 530 | 920 | 1000 |
2 x 6 | 0.7 | 1.2 | 3.08 | 14.50 | 167 | 350 | 1500 |
3 x 6 | 0.7 | 1.2 | 3.08 | 15.00 | 210 | 410 | 1500 |
4 x 6 | 0.7 | 1.2 | 3.08 | 16.00 | 285 | 500 | 1500 |
5 x 6 | 0.7 | 1.2 | 3.08 | 17.50 | 345 | 590 | 1500 |
7 x 6 | 0.7 | 1.4 | 3.08 | 18.20 | 430 | 719 | 1500 |
3 x 10 | 0.8 | 1.2 | 1.83 | 17.50 | 345 | 580 | 1000 |
3 x 10 | 0.8 | 1.4 | 1.83 | 18.50 | 441 | 710 | 1000 |
4 x 10 | 0.8 | 1.4 | 1.83 | 20.50 | 540 | 870 | 750 |
5 x 16 | 0.8 | 1.4 | 1.15 | 20.00 | 520 | 830 | 1500 |
4 x 16 | 0.8 | 1.4 | 1.15 | 21.50 | 671 | 1020 | 750 |
5 x 16 | 0.8 | 1.4 | 1.15 | 23.50 | 825 | 1230 | 750 |
Packing:
Steel wooden drum (fumigation)
Cable length in each drum: 500m/1000m or as per actual cable length requirements.
Drum size:
As per cable length and container size
*In order to quote you accurate price, kindly tell us your needed cable length quantity. Larger quantity, more discount benefit ready for you!
Shipping:
Port: Tianjin, Qingdao, or other ports as per your requireents.
Sea freight:
FOB/C&F/CIF quotation are all available.