low voltage electrical energy cable N2XOH 0,6-1kV 3-1x10, 16mm2
DESCRIPTION
Application:
In low voltage power distribution networks. Special application in places with poor ventilation, direct application in places with public attendance high. It can be installed in ducts in dry and wet places.
Construction:
1. Conductor: Soft copper, class 2.
2. Insulation: Cross linked polyethylene XLPE.
3. Outer sheath: Halogen free thermoplastic compound HFFR-UV.
4. Tape: Polyester tape.
Main features:
The cable has excellent electric properties. The cross-linked polyethylene insulation allows a higher power capacity current under any operation conditions, lower dielectric losses, high insulation resistance. The outer sheath has the following characteristics: Fire retardant, low emission dense smoke and halogen free. Sunlight resistance.
Section:
From 6 mm2 up to 500 mm2.
Packaging:
On non-returnable wooden reels.
National standards
NTP-IEC 60228: Conductors for isolated cables.
NTP-IEC 60502-1: Power cables with extruded insulation and their applications for nominal voltages from 1 kV and 3 kV.
CONSTRUCTION CHARACTERISTICS
Conductor material |
Soft copper, Class 2 IEC 60228 |
Insulating material |
XLPE |
Individual sheath |
Halogen free thermoplastic compound - UV |
Halogen free |
IEC 60754-1 |
DIMENSIONAL CHARACTERISTICS
Cross section [mm²] |
Total no wires |
Conductor diam. [mm] |
Min. insulation thick. [mm] |
Min. outer sheath thick. [mm] |
Height [mm] |
Width [mm] |
Approx. weight [kg/km] |
Cable n2xoh 2X1X16 |
7 |
4.6 |
0.7 |
0.9 |
8.2 |
16.2 |
376 |
Cable n2xoh 2X1X25 |
7 |
5.8 |
0.9 |
0.9 |
9.8 |
19.4 |
572 |
Cable n2xoh 3X1X6 |
7 |
3.0 |
0.7 |
0.9 |
6.5 |
19.2 |
268 |
Cable n2xoh 3X1X10 |
7 |
3.7 |
0.7 |
0.9 |
7.2 |
21.3 |
387 |
Cable n2xoh 3X1X16 |
7 |
4.6 |
0.7 |
0.9 |
8.2 |
24.2 |
564 |
Cable n2xoh 3X1X25 |
7 |
5.8 |
0.9 |
0.9 |
9.8 |
29.1 |
856 |
Cable n2xoh 3X1X35 |
7 |
6.8 |
0.9 |
0.9 |
11 |
32.6 |
1128 |
Cable n2xoh 3X1X50 |
19 |
7.9 |
1.0 |
0.9 |
12.1 |
35.9 |
1487 |
Cable n2xoh 3X1X70 |
19 |
9.5 |
1.1 |
0.9 |
13.9 |
41.3 |
2098 |
Cable n2xoh 3X1X95 |
19 |
11.2 |
1.1 |
1.0 |
15.8 |
47 |
2847 |
Cable n2xoh 3X1X120 |
37 |
12.8 |
1.2 |
1.0 |
17.6 |
52.4 |
3559 |
Cable n2xoh 3X1X150 |
37 |
14.2 |
1.4 |
1.1 |
19.6 |
58.4 |
4323 |
Cable n2xoh 3X1X185 |
37 |
15.8 |
1.6 |
1.2 |
22 |
65.1 |
5436 |
Cable n2xoh 3X1X240 |
37 |
18.0 |
1.7 |
1.2 |
24.3 |
72.5 |
7023 |
Cable n2xoh 3X1X300 |
37 |
20.1 |
1.8 |
1.2 |
26.6 |
79.4 |
8710 |
Cable n2xoh 3X1X400 |
61 |
23.3 |
2.0 |
1.4 |
30.5 |
91.2 |
11418 |
Cable n2xoh 3X1X500 |
61 |
26.2 |
2.2 |
1.5 |
34.1 |
101.9 |
14451 |
ELECTRICAL CHARACTERISTICS
Dielectric strength |
3.5 kV |
Time of application Dielectric strength core to screen DC |
5 min. |
USE CHARACTERISTICS
Maximum operating temperature 90 ° C
Emergency overload temperature 130 ° C
Maximum temperature of the conductor in short-circuit 250 ° C