Product Description
CONCENTRIC AND SPLIT CONCENTRIC CABLES
APPLICATIONS OVERVIEW
Hongda Cables supplies a comprehensive range of concentric and split concentric cables manufactured in accordance with standard BS7870. These aluminium and copper cables are devised for use by Distribution Network Operators (DNOs) to provide the final connection to residential properties. Additional functionality includes use for sub-main distribution and within high-rise buildings and street lighting systems.
The choice between Concentric and Split Concentric cable is determined by the supply type: TN-C-S supply for Concentric and TN-S supply for Split Concentric. These are LSZH cables (low smoke zero halogen) with the outersheath suitable for installations requiring a reduction to the risk to human life or sensitive equipment in the event of fire.
CONCENTRIC CABLES
These cables are used for power supplies with Protective Multiple Earthing (PME) systems, where a combined Protective Earth (PE) and Neutral (N) - together known as the PEN - connects the combined neutral-and-earth to real earth at multiple locations to reduce the risk of electric shock in the event of a broken PEN.
|
Aluminium concentric |
Copper concentric |
Conductor |
Solid aluminium (Class 1) |
Stranded copper conductor (Class 2) |
Insulation |
XLPE (Cross-linked Polyethylene) |
XLPE |
Concentric conductor |
Single layer of plain copper wires |
Single layer of plain copper wires |
Outer sheath |
PVC (Polyvinyl Chloride) |
PVC |
SPLIT CONCENTRIC CABLES
These cables are used when the power supply has separate PE & N conductors and are only combined as PEN near the power source. The Protective Earth and Neutral are not connected after the building entry point.
|
Aluminium split concentric |
Copper split concentric |
Conductor |
Solid aluminium (Class 1) |
Stranded copper (Class 2) |
Insulation |
XLPE |
PVC Type TI1 |
Neutral conductor |
Plain copper wires (Class 1) covered with blue polymeric insulation |
Plain copper wires (Class 1) covered with blue polymeric insulation |
Earth continuity conductor |
Plain copper conductor (Class 1) |
Plain copper conductor (Class 1) |
String separator |
Non-hygroscopic string separator |
Non-hygroscopic string separator |
Outersheath |
PVC TM1 or LSZH |
PVC TM1 |
Voltage: 0.6/1kv.
Operating temperature: Maximum 90°C, minimum -30°C
Common Used Colours:
For insulation: White, Black and Red.
For external jacket: Black
PACKAGING:
Wooden Drum
Or length to the client's requirement.
CONCENTRIC & SPLIT CONCENTRIC CABLE SELECTION
Please contact us for technical support with the right cable selection for your power distribution projects and to discuss your maintenance or project specific requirements. We provide tailored solutions for this cable range which include storage, cutting to length, and 2 days collection as standard.