ACSR Application:
ACSR - The full name: Aluminum Conductor Steel Reinforced. Aluminum Conductor Steel Reinforced is used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.Code Name |
No. / Nominal Dia. of Wire | Approx. Overall Dia. |
Cross Sectional Area |
Approx. Weight |
Nominal Breaking Load |
Max.DC Resistance at 20°C |
|
Aluminum | Steel | ||||||
No./mm | No./mm | mm | mm2 | kg/km | kN | Ω/km | |
Almond | 6/2.50 | 1/2.50 | 7.5 | 34.4 | 119 | 10.5 | 0.9750 |
Apricot | 6/2.75 | 1/2.75 | 8.3 | 41.6 | 144 | 12.6 | 0.8050 |
Apple | 6/3.00 | 1/3.00 | 9.0 | 49.5 | 171 | 14.9 | 0.6770 |
Banana | 6/3.75 | 1/3.75 | 11.3 | 77.3 | 268 | 22.7 | 0.4330 |
Cherry | 6/4.75 | 7/1.60 | 14.3 | 120.0 | 402 | 33.4 | 0.2710 |
Grape | 30/2.50 | 7/2.50 | 17.5 | 182.0 | 677 | 63.5 | 0.1960 |
Lemon | 30/3.00 | 7/3.00 | 21.0 | 262.0 | 973 | 90.4 | 0.1360 |
Lychee | 30/3.25 | 7/3.25 | 22.8 | 307.0 | 1140 | 105.0 | 0.1160 |
Lime | 30/3.50 | 7/3.50 | 24.5 | 356.0 | 1320 | 122.0 | 0.1000 |
Mango | 54/3.00 | 7/3.00 | 27.0 | 431.0 | 1440 | 119.0 | 0.0758 |
Orange | 54/3.25 | 7/3.25 | 29.3 | 506.0 | 1690 | 137.0 | 0.0646 |
Olive | 54/3.50 | 7/3.50 | 31.5 | 587.0 | 1960 | 159.0 | 0.0557 |
Pawpaw | 54/3.75 | 19/2.25 | 33.8 | 672.0 | 2240 | 178.0 | 0.0485 |
Quince | 3/1.75 | 4/1.75 | 5.3 | 16.8 | 95 | 12.7 | 3.2500 |
Raisin | 3/2.50 | 4/2.50 | 7.5 | 34.4 | 195 | 24.4 | 1.5900 |
Sultana | 4/3.00 | 3/3.00 | 9.0 | 49.5 | 243 | 28.3 | 0.8970 |
Walnut | 4/3.75 | 3/3.75 | 11.3 | 77.3 | 380 | 43.9 | 0.5730 |