Customization: | Available |
---|---|
Application: | Construction, Underground, Industrial |
Voltage: | Low and Medium Voltage Cable |
Still deciding? Get samples of US$ 25/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Aluminum URD Cable Underground 600 V 1350 Aluminum URD Service Cable -single core
Secondary underground distribution cables are used to run power from a pad mounted transformer to the service entry or meter of a structure. The cables are rated for installation in underground duct or directly buried in earth. They are offered in single conductor, duplex, triplex, and quadruplex.
Directly buried or installed in ducts for 600V secondary distribution.
Concentric stranded or compressed 1350-H19 aluminum conductor, cross-linked polyethylene insulation.
Secondary URD single conductor 600V cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
• B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation."
• B-901 "Compressed round stranded Aluminum Conductors using single input wire construction."
• Secondary URD single conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
• "USE-2" per UL 854 available upon request.
Item # | Size | Stranding | Insulation Thickness | Approximate O.D | Weight | Ampacity 90ºC Direct Burial | Ampacity 90ºC In Duct | |||
AWG/MCM | mils | mm | inches | mm | LBS/MFT | kg/km | Amps | Amps | ||
Princeton | 6 | 7 | 60 | 1.52 | 0.298 | 7.57 | 45 | 67.0 | 90 | 65 |
Mercer | 4 | 7 | 60 | 1.52 | 0.345 | 8.76 | 64 | 95.2 | 120 | 85 |
Clemson | 2 | 7 | 60 | 1.52 | 0.403 | 10.24 | 93 | 138.4 | 155 | 115 |
Kenyon | 1 | 19 | 80 | 2.03 | 0.522 | 13.26 | 148 | 220.2 | 200 | 150 |
Harvard | 1/0 | 19 | 80 | 2.03 | 0.482 | 12.24 | 122 | 181.5 | 175 | 130 |
Ya le | 2/0 | 19 | 80 | 2.03 | 0.566 | 14.38 | 179 | 266.4 | 225 | 170 |
Tufts | 3/0 | 19 | 80 | 2.03 | 0.616 | 15.65 | 217 | 322.9 | 250 | 195 |
Beloit | 4/0 | 19 | 80 | 2.03 | 0.672 | 17.07 | 265 | 394.3 | 290 | 225 |
Hofstra | 250 | 37 | 95 | 2.41 | 0.748 | 19.00 | 317 | 471.7 | 320 | 250 |
Gonzaga | 300 | 37 | 95 | 2.41 | 0.801 | 20.35 | 371 | 552.0 | 355 | 280 |
Rutgers | 350 | 37 | 95 | 2.41 | 0.851 | 21.62 | 423 | 629.4 | 385 | 305 |
Emory | 500 | 37 | 95 | 2.41 | 0.979 | 24.87 | 579 | 861.6 | 465 | 370 |
Duke | 600 | 61 | 110 | 2.79 | 1.086 | 27.58 | 701 | 1043.1 | 510 | 410 |
Furman | 700 | 61 | 110 | 2.79 | 1.155 | 29.34 | 804 | 1196.4 | 550 | 440 |
Sewanee | 750 | 61 | 110 | 2.79 | 1.188 | 30.18 | 855 | 1272.2 | 580 | 470 |
Fordham | 1000 | 61 | 110 | 2.79 | 1.337 | 33.96 | 1109 | 1650.2 | 670 | 545 |
All drawings, designs, specifications, plans and particulars of weights, sizes and dimensions contained in the technical or commercial documentation of Hongda Cable Company is indicative only and shall not be binding on Hongda Cable Company or be treated as constituting a representation on the part of Hongda Cable Company. All data subject to change without notice.
Contact us
If you are interested in hearing more about our aluminum cables and services, please make use of our contact us page.
Vivian Yuan