Product Description
Power cable 0,6/1 kV with Al conductors, XLPE insulated and HFFR sheathed -NA2XH
Application:
In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.
NA2XH CABLE CONSTRUCTION:
Conductors: Al, class 1 (RE/SE) or class 2 (RM/SM) according to EN 60228
Insulation: XLPE compound DIX 3
Bedding: Extruded elastomere or plastomere compound or plastic tape
Sheath: HFFR compound HM 4
Technical data:
CPR class: Eca
Test voltage: 4 kV
Rated voltage: 0,6/1,0 kV
Bending radius (min): single-core - 15D;
multicore - 12D
Min. laying temperature: -5°C
Max. conductor temperature: 90°C
Max. short-circuit temperature: 250°C
Industry: Building & Construction, Transmission, Distribution & Power Networks
Standard: IEC 60502-1, SI 1516-1
Type: Industrial Cable, LSZH Cable, Power Network & Local Distribution Cable
Product Parameters
NA2XH CABLE DIMENSION:
SINGLE - CORE CABLES: |
NOMINAL CROSS SECTION |
CONDUCTOR CONSTRUCTION |
NOM. THICKNESS OF INSUL. |
OUTER DIAM. (APPROX.) |
METAL WEIGHT |
CABLE WEIGHT (APPROX.) |
MAX. RESISTANCE AT 20°C |
CURRENT CAPACITY IN AIR |
CURRENT CAPACITY IN EARTH |
mm2 |
|
mm |
mm |
kg/km |
kg/km |
ohm/km |
A |
A |
1x16 |
rm |
0,7 |
9,5 |
46,2 |
122 |
1,910 |
- |
- |
1x25 |
rm |
0,9 |
11,9 |
72,5 |
175 |
1,200 |
106 |
114 |
1x35 |
rm |
0,9 |
13,0 |
101,5 |
206 |
0,868 |
130 |
136 |
1x50 |
rm |
1,0 |
14,9 |
145,0 |
267 |
0,641 |
161 |
162 |
1x70 |
rm |
1,1 |
17,0 |
203,0 |
358 |
0,443 |
204 |
199 |
1x95 |
rm |
1,1 |
18,9 |
275,5 |
451 |
0,320 |
252 |
238 |
1x120 |
rm |
1,2 |
20,7 |
348,0 |
546 |
0,253 |
295 |
272 |
1x150 |
rm |
1,4 |
22,7 |
435,0 |
655 |
0,206 |
339 |
305 |
1x185 |
rm |
1,6 |
25,1 |
536,5 |
800 |
0,164 |
395 |
347 |
1x240 |
rm |
1,7 |
27,6 |
696,0 |
987 |
0,125 |
472 |
404 |
1x300 |
rm |
1,8 |
31,9 |
870,0 |
1324 |
0,100 |
547 |
457 |
1x400 |
rm |
2,0 |
34,9 |
1160,0 |
1640 |
0,0778 |
643 |
525 |
1x500 |
rm |
2,2 |
39,3 |
1450,0 |
2030 |
0,0605 |
754 |
601 |
1x630 |
rm |
2,4 |
44,1 |
1827,0 |
2400 |
0,0469 |
882 |
687 |
1x800 |
rm |
2,6 |
46,5 |
2320,0 |
2505 |
0,0367 |
1019 |
776 |
1x1000 |
rm |
2,8 |
52,0 |
2900,0 |
3115 |
0,0291 |
1157 |
865 |
THREE - CORE CABLES: |
NOMINAL CROSS SECTION |
CONDUCTOR CONSTRUCTION |
NOM. THICKNESS OF INSUL. |
OUTER DIAM. (APPROX.) |
METAL WEIGHT |
CABLE WEIGHT (APPROX.) |
MAX. RESISTANCE AT 20°C |
CURRENT CAPACITY IN AIR |
CURRENT CAPACITY IN EARTH |
mm2 |
|
mm |
mm |
kg/km |
kg/km |
ohm/km |
A |
A |
3x16 |
rm |
0,7 |
16,5 |
139,2 |
397 |
1,910 |
- |
- |
3x25 |
rm |
0,9 |
20,0 |
217,5 |
587 |
1,200 |
102 |
112 |
3x35 |
rm/sm |
0,9 |
22,5 |
304,5 |
531 |
0,868 |
126 |
135 |
3x50 |
rm |
1,0 |
27,6 |
435,0 |
1007 |
0,641 |
149 |
158 |
3x70 |
rm |
1,1 |
30,6 |
609,0 |
1401 |
0,443 |
191 |
196 |
3x95 |
rm |
1,1 |
33,8 |
826,5 |
1801 |
0,320 |
234 |
234 |
3x120 |
rm |
1,2 |
37,5 |
1044,0 |
2226 |
0,253 |
273 |
268 |
3x50 |
se/sm |
1,0 |
26,0 |
435,0 |
720 |
0,641 |
149 |
158 |
3x70 |
se/sm |
1,1 |
29,7 |
609,0 |
963 |
0,443 |
191 |
196 |
3x95 |
se/sm |
1,1 |
33,4 |
826,5 |
1246 |
0,320 |
234 |
234 |
3x120 |
se/sm |
1,2 |
37,1 |
1044,0 |
1545 |
0,253 |
273 |
268 |
3x150 |
se/sm |
1,4 |
41,2 |
1305,0 |
1916 |
0,206 |
311 |
300 |
3x185 |
se/sm |
1,6 |
45,7 |
1609,5 |
2347 |
0,164 |
360 |
342 |
3x240 |
se/sm |
1,7 |
51,6 |
2088,0 |
2987 |
0,125 |
427 |
398 |
3x300 |
se/sm |
1,8 |
56,7 |
2160,0 |
3663 |
0,100 |
507 |
457 |
FOUR - CORE CABLES |
NOMINAL CROSS SECTION |
CONDUCTOR CONSTRUCTION |
NOM. THICKNESS OF INSUL. |
OUTER DIAM. (APPROX.) |
METAL WEIGHT |
CABLE WEIGHT (APPROX.) |
MAX. RESISTANCE AT 20°C |
CURRENT CAPACITY IN AIR |
CURRENT CAPACITY IN EARTH |
mm2 |
|
mm |
mm |
kg/km |
kg/km |
ohm/km |
A |
A |
3x70+35 |
sm/sm |
1,1/0,9 |
28,8 |
655,4 |
935 |
0,443/0,868 |
191 |
196 |
3x95+50 |
sm/sm |
1,1/1,0 |
32,2 |
899,0 |
1120 |
0,320/0,641 |
234 |
234 |
3x120+70 |
sm/sm |
1,2/1,1 |
34,6 |
1145,5 |
1430 |
0,253/0,443 |
273 |
268 |
3x150+70 |
sm/sm |
1,4/1,1 |
38,5 |
1450,0 |
1950 |
0,206/0,443 |
311 |
300 |
3x185+95 |
sm/sm |
1,6/1,1 |
42,4 |
1812,5 |
2345 |
0,164/0,320 |
360 |
342 |
3x240+120 |
sm/sm |
1,7/1,2 |
47,2 |
2363,5 |
2980 |
0,125/0,253 |
427 |
398 |
4x35 |
sm |
0,9 |
25,9 |
406,0 |
690 |
0,868 |
126 |
135 |
4x50 |
se/sm |
1,0 |
28,4 |
580,0 |
832 |
0,641 |
149 |
158 |
4x70 |
se/sm |
1,1 |
32,4 |
812,0 |
1234 |
0,443 |
191 |
196 |
4x95 |
se/sm |
1,1 |
35,6 |
1102,0 |
1460 |
0,320 |
234 |
234 |
4x120 |
se/sm |
1,2 |
40,6 |
1392,0 |
1861 |
0,253 |
273 |
268 |
4x150 |
se/sm |
1,4 |
44,8 |
1740,0 |
2386 |
0,206 |
311 |
300 |
4x185 |
se/sm |
1,6 |
49,2 |
2146,0 |
2866 |
0,164 |
360 |
342 |
4x240 |
se/sm |
1,7 |
54,9 |
2784,0 |
3616 |
0,125 |
427 |
398 |
4x300 |
se/sm |
1,8 |
58,8 |
3480,0 |
4500 |
0,100 |
507 |
457 |
FOUR - CORE CABLES WITH CONTROL CONDUCTOR |
NOMINAL CROSS SECTION |
CONDUCTOR CONSTRUCTION |
NOM. THICKNESS OF INSUL. |
OUTER DIAM. (APPROX.) |
METAL WEIGHT |
CABLE WEIGHT (APPROX.) |
MAX. RESISTANCE AT 20°C |
CURRENT CAPACITY IN AIR |
CURRENT CAPACITY IN EARTH |
mm2 |
|
mm |
mm |
kg/km |
kg/km |
ohm/km |
A |
A |
4x16+1,5 |
re/rm |
0,7 |
22,1 |
185,6 |
615 |
1,910 |
- |
- |
4x25+1,5 |
re/rm |
0,9 |
26,2 |
290,0 |
870 |
1,200 |
102 |
112 |
4x35+1,5 |
re/rm |
0,9 |
28,9 |
406,0 |
1074 |
0,868 |
126 |
135 |
4x35+1,5 |
sm |
0,9 |
23,1 |
406,0 |
630 |
0,868 |
126 |
135 |
4x50+1,5 |
se/sm |
1,0 |
26,0 |
580,0 |
847 |
0,641 |
149 |
158 |
4x70+1,5 |
se/sm |
1,1 |
30,0 |
812,0 |
1135 |
0,443 |
191 |
196 |
4x95+1,5 |
se/sm |
1,1 |
33,6 |
1102,0 |
1480 |
0,320 |
234 |
234 |
4x120+1,5 |
se/sm |
1,2 |
37,3 |
1392,0 |
1826 |
0,253 |
273 |
268 |
4x150+1,5 |
se/sm |
1,4 |
42,0 |
1740,0 |
2282 |
0,206 |
311 |
300 |
4x185+1,5 |
se/sm |
1,6 |
46,3 |
2146,0 |
2766 |
0,164 |
360 |
342 |
4x240+1,5 |
se/sm |
1,7 |
52,1 |
2784,0 |
3572 |
0,125 |
427 |
398 |
4x300+1,5 |
se/sm |
1,8 |
56,8 |
3480,0 |
4374 |
0,100 |
507 |
457 |
SIGNAL CU WIRE: Nominal cross section: 1,5 mm² Max. resistance at 20°C :12,1 Ω/km Nom. thicknss of insul. :0,7mm Outer diameter :2,9mm
FIVE - CORE CABLES |
NOMINAL CROSS SECTION |
CONDUCTOR CONSTRUCTION |
NOM. THICKNESS OF INSUL. |
OUTER DIAM. (APPROX.) |
METAL WEIGHT |
CABLE WEIGHT (APPROX.) |
MAX. RESISTANCE AT 20°C |
CURRENT CAPACITY IN AIR |
CURRENT CAPACITY IN EARTH |
mm2 |
|
mm |
mm |
kg/km |
kg/km |
ohm/km |
A |
A |
5x16 |
rm |
0,7 |
23,4 |
232,0 |
625 |
1,910 |
- |
- |
5x25 |
rm |
0,9 |
28,2 |
362,5 |
950 |
1,200 |
102 |
112 |
5x35 |
rm |
0,9 |
31,0 |
507,5 |
1195 |
0,868 |
126 |
135 |
5x50 |
rm |
1,0 |
36,8 |
725,0 |
1540 |
0,641 |
149 |
158 |
5x70 |
rm |
1,1 |
42,8 |
1015,0 |
2240 |
0,443 |
191 |
196 |
5x95 |
rm |
1,1 |
48,5 |
1377,5 |
3015 |
0,320 |
234 |
234 |
5x120 |
rm |
1,2 |
53,6 |
1740,0 |
3580 |
0,253 |
273 |
268 |
NA2XH CABLE SELECTION:
In addition to our portfolio of European power cables we also supply British standard low voltage power cables including armoured cable with its LSZH outer sheathing. Our technical has a wealth of experience in providing support in the selection of the right cable for your application. Please call to discuss your specific application.
If you have another question, pls feel free to contact us below