Audited by an independent third-party inspection agency
1 ..... stranded (RM) aluminium wires
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... screen of copper wires
6 ..... outer sheath of polyvinylchloride (PVC), red
DIN VDE0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Test voltage | 6 / 10kV | [kV] | 21 / 5 min. |
12 / 20kV | [kV] | 42 / 5 min. | |
18 / 30kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section | Aluminum Figure | Copper Figure | Overall diameter appr. | Weight appr | Current carrying capacity ground | Current carrying capacity air |
mm2 | kg/km | kg/km | mm | kg/km | A | A |
1x50 RM/16 | 147,0 | 190 | 28 | 950,0 | 172 | 185 |
1x70 RM/16 | 206,0 | 190 | 30 | 1050,0 | 210 | 231 |
1x95 RM/16 | 279,0 | 190 | 31 | 1300,0 | 251 | 280 |
1x120 RM/16 | 353,0 | 190 | 33 | 1100,0 | 285 | 323 |
1x150 RM/25 | 441,0 | 295 | 34 | 1500,0 | 319 | 366 |
1x185 RM/25 | 544,0 | 295 | 36 | 1650,0 | 361 | 420 |
1x240 RM/25 | 706,0 | 295 | 39 | 1850,0 | 417 | 496 |
1x300 RM/25 | 882,0 | 295 | 41 | 2100,0 | 471 | 569 |
1x400 RM/25 | 1176,0 | 410 | 44 | 2550,0 | 535 | 660 |