ITEM |
SPECIFICATION (PARTICULARS |
UNIT |
Data |
1 |
Insulation Voltage |
V |
600/1000 |
2 |
Conductor size |
mm² |
16 |
3 |
Phase Conductor material |
N/A |
Hard drawn Aluminium conductor
-Single core |
4 |
Insulation Material |
N/A |
XLPE |
5 |
Earth wire material type |
N/A |
Bare Aluminium conductor |
6 |
Rip Chord |
N/A |
Nylon |
7 |
Reference Standards |
N/A |
SANS 1507, NRS 063, IEC 60502/228 ESI 09-7 |
8 |
Phase conductor Insulation thickness |
mm |
1.0 |
|
Construction (Phase conductor) |
|
|
9 |
Structure |
mm |
Single core |
10 |
Insulation Thickness |
mm |
1.0 |
11 |
Reference Insulation O.D |
mm |
7.1 |
|
Construction (Earth Wire) |
|
|
12 |
Structure |
Numbers |
12 |
13 |
Wire structure |
N/A |
12/1.7 |
|
Construction (Pilot/Communication Wires) |
|
|
14 |
Structure |
mm² |
4X0.5 |
15 |
Reference Insulation O.D |
mm |
1.13 |
16 |
Conductor material |
N/A |
Copper |
17 |
Insulation Material |
N/A |
LLPDE/XLPE |
18 |
Number of conductors |
Numbers |
4 |
|
Construction (Sheath) |
|
|
19 |
Nominal Thickness |
mm |
1.6 |
20 |
Reference Insulation O.D |
mm |
14.5 |
21 |
Sheath Material |
N/A |
LLPE Black UV stable/HQ PVC |
|
Insulation material colours |
|
|
22 |
Phase conductor |
N/A |
Red |
23 |
Pilot wires (04) |
N/A |
Red, Green, White, Blue |
24 |
Sheath |
N/A |
Black |
|
Performance (Electrical Characteristics) |
|
|
25 |
Phase Conductor - Maximum resistance at |
|
≤1.91 |
26 |
Earth Wires - - Maximum resistance at |
|
≤7.40 |
27 |
Pilot Wires - Maximum resistance at 20 |
|
≤36 |
1.Phase conductor:Solidal 16sqm aluminum wire (diameter 4.50mm)
2.Insulation :XLPE (nominal thickness :1.0mm,color :red)
3.Pilot core plain annealed copper wire 0.5sqm(diameter 0.8mm )
4.Pilot core insulation diameter min 1.13(the actual approximation :1.7mm) LLDPE
5.Neutral conductor :solidal aluminum wire (12/1.31)
6.Binder tape :non-hygroscopic tape
7.Ripcord
8.Sheathed:LLDPE (nominal thickness :1.6mm, color black )
Characteristic
Voltage Rating |
600V / 1000V |
Temperature Limits |
-15ºC to +90ºC |
Minimum Bending Radius |
As per cable manufacturer datasheet/td> |
Installation Environment |
Should not be installed at temperatures below 0ºC or above 60ºC |
Concentric cable PVC-size
CCC CODE |
CONDUCTOR SIZE |
STRANDING |
WEIGHT |
OVERALL DIAMETER |
GLAND SIZE |
|
mm² |
mm² |
kg/km |
mm |
|
4 SPLITCON |
4 |
7/0.85 |
206 |
9.6 |
205 |
6 SPLITCON |
6 |
7/1.04 |
281 |
11.4 |
20 |
10 SPLITCON |
10 |
7/1.35 |
394 |
11.4 |
20 |
16 SPLITCON |
16 |
7/1.70 |
583 |
14.6 |
25 |
25 SPLITCON |
25 |
7/2.14 |
843 |
18.7 |
32 |
35 SPLITCON |
35 |
7/2.52 |
1300 |
23 |
40 |
Concentric cable PVC - current carrying capacity
NOMINAL CROSS SECTIONAL AREA (MM² ) |
CLIPPED DIRECT AMPS |
IN CONDUIT ON WALL AMPS |
IN AIR AMPS |
4 |
41 |
37 |
42 |
6 |
50 |
46 |
51 |
10 |
68 |
63 |
70 |
16 |
99 |
88 |
100 |
25 |
130 |
117 |
135 |
35 |
120 |
110 |
129 |
Concentric cable PVC - Electrical Characteristics
NOMINAL CROSS SECTIONAL AREA (MM2 ) |
MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C - PHASE OHMS/KM |
MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C - NEUTRAL OHMS/KM |
MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C - EARTH OHMS/KM |
4 |
4.61 |
4 |
4.80 |
6 |
3.08 |
3.15 |
3.15 |
10 |
1.83 |
1.90 |
1.90 |
16 |
1.15 |
1.20 |
1.20 |
25 |
0.727 |
0.76 |
0.76 |
35 |
0.524 |
0.55 |
0.55 |