SIP Aluminum Overhead Cable 4*10 4*16

Product Details
Customization: Available
Application: Overhead
Voltage: Low and Medium Voltage Cable
Still deciding? Get samples of US$ 100/Meter
Request Sample
Manufacturer/Factory

360° Virtual Tour

Diamond Member Since 2017

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
Quality Assurance
The supplier provides quality assurance
Management Certification
The supplier has quality management system certification, including:
ISO9001:2015 certificate
to see all verified strength labels (21)
  • SIP Aluminum Overhead Cable 4*10 4*16
  • SIP Aluminum Overhead Cable 4*10 4*16
  • SIP Aluminum Overhead Cable 4*10 4*16
  • SIP Aluminum Overhead Cable 4*10 4*16
  • SIP Aluminum Overhead Cable 4*10 4*16
  • SIP Aluminum Overhead Cable 4*10 4*16
Find Similar Products

Basic Info.

Model NO.
SIP
Current
DC Cable
Insulation Material
XLPE
Sheath Material
No Jacket
Material Shape
Round Wire
Wire Core Material
Aluminum
Certification
ISO, CCC
Model
ABC
Brand
Hongda
Cores
2 3 4 5
Transport Package
on The Drum or on The Pallent
Specification
10 16 25 35 50 70 95 120
Trademark
hongda
Origin
Henan
HS Code
8544492100
Production Capacity
10000m/Day

Product Description





Self supporting insulated wires (Aerial Bundled Conductor) SIP per GOST R 52373-2005 and TU 16-705.500-2006
(TU 16-705.500-2006 used instead of TU 16.К71-268-98 and TU 16.К71- 272-98)


SIP-1 - self supporting wire with Al cores, with insulation from light-stabilized cross-linked PE,
neutral messenger non-insulated core from Al alloy.
SIP-2 - the same.

SIP-3 - protected self supporting wire, with conducting core from Al alloy with insulation from lightstabilized cross-linked PE.
SIP-4 - protected self supporting wire, without currier element, with Al conducting cores with insulation from light-stabilized cross-linked PE.


CONSTRUCTION
1. CONDUCTING CORE - Al round core  for all cross-section the core is compacted multiwire, the quantity of wire in phase core. Outer diameter of conducting core and its electrical resistance shown in bellow table:
Nominal cross-section of phase core, mm2 Number of wires in the core, units. Outer diameter of conducting core, mm Electrical resistance of 1 km of phase core to DC, ohm not more
Min. Max.
 16  7  4,6  5,1  1,910
 25  7  5,7  6,1  1200
 35  7  6,7  7,1  0,868
 50  7  7,85  8,35  0,641
 70  7  9,45  9,95  0,443
 95  7  11,1  11,7  0,320
 120  19  11,1  13,1  0,253
 150  19  14,0  14,5  0,206
 185  19  15,45  16,15  0,164
 240  19  17,75  18,45  0,125

 
2. NEUTRAL MESSENGING CORE - form Al alloy, round core, stranded from round wires,
compacted. Nominal cross-sections, number of wires in the core, outer diameter of core, its burst capacity and electrical resistance are specified in the bellow table:
Nominal cross-section of phase core, mm2 Number of wires in the core, units. Outer diameter of conducting core, mm Electrical resistance of 1 km of phase core to DC, ohm not more
Min. Max.
 25  7  5,7  6,1  1,380
 35  7  6,7  7,1  0,986
 50  7  7,85  8,35  0,720
 54,6  7  9,2  9,6  0,630
 70  7  9,45  9,95  0,493
 95  7  11,1  11,7  0,363
 120  19  12,2  12,9  0,288
 150  19  13,9  14,5  0,236
 185  19  15,75  16,15  0,188
 240  19  17,75  18,45  0,145
 
3. INSULATION - in SIP-1 the neutral core is not insulated. In other conductors the insulation made from light-stabilized cross-linked PE. Insulated phase cores have the distinctive coloring. Insulation thickness is shown in the following table:
Types of wire
 
Nominal isulation thickness, mm
16 25 35 50 54,6 70 95 120 150 185 240
SIP-1 1,3 1,3 1,3 1,5 1,5 1,7 1,7 1,7 1,7 1,9 1,9
SIP-2
SIP-3 20 kV 2,3
SIP-3 35 kV 3,5
SIP-4 1,3 1,3  
 
APPLICATION
SIP-1 - for overhead transmission lines (TL) and linear TL deviations in atmosphere types I and II as per GOST 15150-69
SIP-2 - for overhead transmission lines (TL) and linear TL deviations in atmosphere types I and II as per GOST 15150-69 , including sea coasts, salt lakes shores, in industrial areas

SIP-3 - for TL with nominal voltage 10-35 kV in atmosphere types II and III as per GOST 15150-69 , including sea coasts, salt lakes shores, in industrial areas
SIP-4 - for TL deviations to entry and for laying in walls of buildings and engineering structures in
atmosphere types II and III as per GOST 15150-69

 
Mark and rated voltage wire Number and nominal cross-phase and zero bearing veins sht.h mm2 Estimate the outer diameter of wire, mm Estimated weight of 1 km of wire, kg
SIP-1 0,6 / 1 kV 1х16+1х25 15 135
3х16+1х25 22 270
3х25+1х35 26 390
3х35+1х50 30 530
3х50+1х50 32 685
3х50+1х70 35 740
3х70+1х70 37 930
3х70+1х95 41 990
3х95+1х70 41 1190
3х95+1х95 43 1255
3х120+1х95 46 1480
3х150+1х95 48 1715
3х185+1х95 52 2330
3х240+1х95 56 2895
SIP-2 0,6 / 1 kV 3х16+1х25 24 308
3х16+1х54,6* 28 427
3х25+1х35 27 424
3х25+1х54,6* 30 512
3х35+1х50 31 571
3х35+1х54,6* 32 606
3х50+1х50 34 727
3х50+1х54,5* 35 762
3х50+1х70 36 798
3х70+1х54,6* 39 973
3х70+1х70 40 1010
3х70+1х95 41 1087
3х95+1х70 43 1240
3х95+1х95 45 1319
3х120+1х95 48 1553
3х150х1х95 50 1787
3х185+1х95 55 2403
3х240+1х95 60 2968
SIP-3 20 кV 1х35 12 165
1х50 13 215
1х70 15 282
1х95 16 364
1х120 18 445
1х150 19 540
1х185 24 722
1х240 24 950
SIP-3 20 кV 1х35 14 209
1х50 16 263
1х70 17 334
1х95 19 421
1х120 20 518
1х150 22 618
1х185 24 808
1х240 26 1045
SIP-4 0,6/1 кV 2х16 15 139
4х16 18 278