Customization: | Available |
---|---|
Type: | Insulated |
Conductor Type: | Stranded |
Still deciding? Get samples of US$ 0/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
STANDART:
IEC 60502, VDE 0276/620
DESCRIPTION:
Cu / Al conductors • XLPE insulation • Cu screen • PE sheath
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are su The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
CABLE CONSTRUCTION |
TECHNICAL DATA |
||
CONSTRUCTION | According to IEC 60502 and DIN VDE 0276-620 | CONDUCTOR RESISTANCE | According to BDS904 (IEC60228) class 2 and VDE 0295 class 2 |
CONDUCTOR | Cu and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 | OPERATING TEMPERATURE | 90ºC continuous operation |
SHORT CIRCUIT TEMPERATURE | 250ºC ( 5 sec.) | ||
INNER SEMI- CONDUCTIVE LAYER | semi-conductive XLPE compound | OVERLOAD TEMPERATURE | 130ºC/100h per year max./ |
INSULATION | XLPE compound | ||
OUTER SEMI- CONDUCTIVE LAYER | semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound | NOMINAL VOLTAGE UO/U | 6/10; 12/20; 18/30 kV |
HIGHEST SYSTEM VOLTAGE UO/U, NO MORE THAN | 6/10; 12/20; 18/30 kV 12kV; 24kV; 36kV | ||
TEST VOLTAGE AC (») - 5 MIN DC (=) - 15 MIN |
6/10; 12/20; 18/30kV 21kV; 42kV; 63kV 67kV; 134kV; 201kV |
||
METAL SCREEN | Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. | BENDING RADIUS | 15 x Dcable |
LEVEL OF PARTIAL DISCHARGE AT 2*UO | max. 5 pc/ 2 pc | ||
SEPARATING LAYER | Layer of plastic tape | TEMPERATURE OF LAYING | no less than -20ºC |
SHEATH | PVC compound | TEMPERATURE OF EXPLOITATION | -30ºC to 50ºC |
TESTS | according to IEC 60502-2 or DIN VDE 0276-620 | ||
COLOR | black | FORCE OF STRAIN IN LAYING N MAX. | Al cores - 30*n*S core Cu cores - 50*n*S core, -n-number of cores and -S-nominal cross section of cores in mm |
CONDUCTOR MATERIAL |
Aluminium |
---|---|
CONDUCTOR CLASS |
Circular, Stranded Class 2 |
INSULATION |
XLPE - Cross-linked Polyethylene |
METALLIC SCREEN |
Copper Wire Screen - Annealed Copper Wires Helicaly Wound and Equalising Copper Tape Applied in Open Counter-helix. Plastic Tape is Applied Over Screen |
OVERSHEATH |
LSHF Low Smoke Halogen Free Thermoplastic Compound, Polyolefin Type DMZ2 |
OVERSHEATH COLOUR |
Black |
CABLE DESIGNATION |
Al, Cu Tape Screen, PO, XLPE |
TEST VOLTAGE |
3.5xUo |
CONDUCTOR OPERATING TEMP |
90°C (nominal) to 120°C (2) |
MAX SHORT-CIRCUIT TEMP |
250°C (t<5s) |
AMBIENT TEMPERATURE |
Cables in Air 30°C |
MAX PULLING FORCE (N) |
30xConductor Cross-section [mm2] Over Conductor (N) |
BEDDING |
LSHF Low Smoke Halogen Free Thermoplastic Compound |
FIRE RETARDANT |
Bunch of Cables Vertically Mounted on a Ladder, Length of Charred Cable <2.5m |
Packing shipping
If you have another question, pls feel free to contact us below