4 Core 16sqmm ABC cable Application
Used to supply power,usually from a pole-mounted transformer, to the user's service head where connection to the service entrance.To be used at 600V or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated or 90°C for cross linked.
4 Core 16sqmm ABC cable Standard
NFC 33-209
4 Core 16sqmm ABC cable Technical Data
Temperature range:
during installation: -5 °C
operating temperature: -30 °C up to +90 °C
at short circuit of max. 5 s: 130 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 4 kV
Minimal inner bending radius: 12D
4 Core 16sqmm ABC cable Structure
Conductor |
Aluminium conductor, round stranded compressed (RM). |
Insulation |
XLPE. Load-bearing / neutral core - marked with standard and producers phase core - marked with digits 1, 2, 3. |
Assembly |
Cores and the neutral, conductor stranded together in right-hand lay, additionally 1, 2 or 3 cores of reduced cross section can be co-stranded. |
4 Core 16sqmm ABC Cable Parameter
TECHNICAL DATA SHEET | |||
Câble préassemblé torsadé 4x16mm² | |||
No. | Description | Unit | Data Provided |
1 | Standards Reference | IEC 60502-1,NFC 33 209 | |
2 | Voltage | Volt | 600/1000 |
3 | Type of cable | mm² | 4x16 |
4 | Material of conductor | Stranded Aluminum wire | |
Stranding no. of wires in conductor | No. | 7 | |
Approx.diameter of conductor | mm | 5.0 | |
5 | Material of insulation | Black XLPE | |
Norminal thickness of insulation | mm | 1.2 | |
Approx.diameter of insulated conductor | mm | 8.8 | |
6 | Approx.overall diameter of completed cable | mm | 18 |
7 | Maximum d.c. resistance of conductor of cable at 20°C | ohm/km | 1.91 |
8 | Approx.weight of completed cable | kg/km | 260 |