3.3 kV 3 core SWA PVC cable max. 90° C - XLPE insulated, PVC sheathed, medium voltage power cable - Applications
This medium voltage power cable may be used for power networks, in fixed installation outdoors, in cable ducts, or directly in the ground.
The steel wire armoured cable is the accepted standard for underground installations, designed for use in mains supply electricity.
These cables are provided with mechanical protection and are therefore suitable for external use, direct burial and areas where sudden mechanical stress are expected.
1. Construction Characteristics |
|
Conductor material: | Copper - IEC60228 |
Conductor shape: | 16mm² & 25mm² - Circular |
35mm² - Sector-shaped or Circular | |
50mm² up to 400mm² - Sector-shaped | |
Conductor flexibility: | Stranded class 2 |
Insulation: | XLPE (Cross-linked Polyethylene) - IEC60502 |
Inner sheath: | PVC - IEC60502 |
Armour type: | Galvanized steel wires |
Outer sheath: | PVC - IEC60502 |
Colour: | Black |
Lead free: | Yes |
2. Electrical Characteristics |
|
Rated Voltage Uo/U (Um): | 1900/3300 Volts - BS5467 IEC60502-1 |
Usage Characteristics |
|
Minimum installation temperature: | 0°C |
Maximum installation temperature: | +60°C |
Installation type: | Outdoor - Direct burial |
Minimum operating temperature: | -15°C |
Maximum operating temperature: | 90°C |
Short-circuit max. conductor temperature: | 250°C |
Flame retardant: | BS EN 60332 / IEC 60332-1 |
Bending radius: | 8 x Overall diameter |
Part Number | Cross Section | Stranding | Approx Weight | Approx Overall Diameter | Gland Size | Single Cleat | Nom. Max. DC-resist conductor 20â° C | Current Rating Direct in ground |
(mm²) | (mm) | KG/KM | (mm) | (mm) | (Ohm/km) | (Amp) | ||
3.3SWAPVC3X16 | 3 x 16 | 7/1.70 | 1690 | 29.2 | 32 | 1.2 | 1.15 | 75 |
3.3SWAPVC3X25 | 3 x 25 | 7/2.14 | 2170 | 32.3 | 32 | 1.4 | 0.727 | 96 |
3.3SWAPVC3X35 | 3 x 35 | 7/2.52 | 2550 | 35.0 | 40 | 1.4 | 0.524 | 115 |
3.3SWAPVC3X50 | 3 x 50 | 19/1.78 | 3130 | 34.8 | 40 | 1.4 | 0.387 | 135 |
3.3SWAPVC3X70 | 3 x 70 | 19/2.14 | 3910 | 38.0 | 40 | 1.6 | 0.268 | 167 |
3.3SWAPVC3X95 | 3 x 95 | 19/2.52 | 4845 | 41.4 | 50s | 1.8 | 0.193 | 197 |
3.3SWAPVC3X120 | 3 x 120 | 37/2.03 | 6185 | 45.64 | 50s | 1.8 | 0.153 | 223 |
3.3SWAPVC3X150 | 3 x 150 | 37/2.25 | 7195 | 48.4 | 50 | 2.0 | 0.124 | 251 |
3.3SWAPVC3X185 | 3 x 185 | 37/2.52 | 8455 | 51.75 | 50 | TC9 | 0.0991 | 281 |
3.3SWAPVC3X240 | 3 x 240 | 61/2.25 | 10485 | 56.7 | 63s | TC9 | 0.0754 | 324 |
3.3SWAPVC3X300 | 3 x 300 | 61/2.52 | 12485 | 60.95 | 63 | TC10 | 0.0601 | 365 |
3.3SWAPVC3X400 | 3 x 400 | 61/2.85 | 15370 | 66.2 | 75s | TC11 | 0.0470 | - |
Ambient air temperature: 30 °C
Ground temperature: 20 °C
Maximum conductor temperature: 90 °C
Where a conductor operates at a temperature exceeding 70 °C it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see Regulation 512.1.2).
Where cables in the above table are connected to the equipment or accessories designed to operate at a temperature not exceeding 70 °C, the current rating given in the equivalent table for 70 °C thermoplastic insulated cables (Table 4D4A) must be used (also see Regulation 523.1).