• Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable
  • Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable
  • Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable
  • Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable
  • Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable
  • Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable

Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable

Type: Insulated
Conductor Type: Solid
Application: Overhead, Heating, Underground, Laying Tubes, Under and Surface Mounting
Conductor Material: Copper
Sheath Material: No Sheath
Insulation Material: PVC
Samples:
US$ 0.5/Meter 1 Meter(Min.Order)
| Request Sample
Customization:

360° Virtual Tour

Diamond Member Since 2017

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
vob cable
Material Shape
Round Wire
Range of Application
in Dry Rooms, Instruments, Switches and Distributi
Certification
ISO9001, CE, CCC, SGS
Brand
Hongda
Central Conductor
Fine Solid Copper
Insulation
Polyvinyl Chloride (PVC)
Rated Voltage
450/750V
Standard
IEC 60227, IEC60228
Transport Package
a: Roll of 100 M B: Reel of 1500 M.
Specification
0.5mm2 to 10mm2
Trademark
Hongda or as customer require
Origin
China
HS Code
8544492900
Production Capacity
100km/Day

Product Description

Cable VOB, H07V-U / H07V-R Electrical Wire Electric cable

Operating Temperature: -15°C to 70°C
Final Short Circuit
160°C for cable < 300mm2
140°C for cable >300mm2
Test Voltage: 2.5kV For 5 minutes

H07V-R / H07V-U

Application and Description

H05 V-U/(H)05 V-U
These insulated wires are determined for the installation to the inside of apparatus as well as for the protective laying to the lightings, in dry rooms, in production facilities, switch and distributor boards, in tubes, under and surface mounting of plasters.

H07 V-U/(H)07 V-U/H07V-R
These insulated wires are suitable for laying tubes, under and surface mounting of plasters and also in closed installation conduits. These are not allowed to install for direct laying in cable trays, channels or tanks.

These types are permitted for the inner wiring of equipment, distributor and switchboards and also for protective laying to the lightings with a nominal voltage up to 1000 V alternating current or up to 750 V direct current against ground.
 

Standard and Approval

  • NF C 32-201-3, IEC 60227, LEC 60228

Cable Construction

Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable
Solid bare copper single wire
Solid to DIN VDE 0295 cl-1 and IEC 60228 cl-1
Special PVC TI1 core insulation
H05V-U (20, 18 & 17 AWG)
H07V-U (16 AWG and Larger)


PVC H05V-U / H07V-U VOB Cable Technical Characteristics

Working voltage 300/500v (H05V-U)
Working voltage 450/750v (H07V-U)
Test voltage 2000V(H05V-U)/2500V (H07V-U)
Flexing bending radius 15 x O
Static bending radius 15 x O
Flexing temperature -5oC to +70oC
Static temperature -30oC to +90oC
Short circuit temperature +160oC
Flame retardant NF C 32-070
Insulation resistance 10 MΩ x km

Cable Parameter

H07V-K PVC electric wire 450/750V Specification:

AWG No. of Cores x
Nominal Cross Sectional Area
# x mm²
Nominal
Overall Diameter
Nominal
Copper Weight kg/Km
Nominal Weight
kg/Km
16(30/30) 1 x 1.5 3.1 14.4 20
14(50/30) 1 x 2.5 3.6 24 31
12(56/28) 1 x 4 4.3 38 48
10(84/28) 1 x 6 4.9 58 69
8(80/26) 1 x 10 6.4 96 121
6(128/26) 1 x 16 8.1 154 211
4 (200/26) 1 x 25 9.8 240 303
2 (280/26) 1 x 35 11.1 336 417
1 (400/26) 1 x 50 13.1 480 539
2/0 (356/24) 1 x 70 15.5 672 730
3/0 (485/24) 1 x 95 17.2 912 900
4/0 (614/24) 1 x 120 19.7 1152 1135
300 MCM (765/24) 1 x 150 21.3 1440 1410
350 MCM (944/24) 1 x 185 23.4 1776 1845
500MCM(1225/24) 1 x 240 27.1 2304 2270

H07V-U PVC Electric Cable 450/750V Specification:

AWG No. of Cores x
Nominal Cross Sectional Area
# x mm²
Nominal
Overall Diameter
Nominal
Copper Weight
kg/Km
Nominal Weight
kg/Km
20 1 x 0.5 2.1 4.8 9
18 1 x 0.75 2.2 7.2 11
17 1 x 1 2.4 9.6 14
16 1 x 1.5 2.9 14.4 21
14 1 x 2.5 3.5 24 33
12 1 x 4 3.9 38 49
10 1 x 6 4.5 58 69
8 1 x 10 5.7 96 115

H07V-R PVC electric wire Cable 450/750V Specification:

AWG No. of Cores x
Nominal Cross Sectional Area
# x mm²
Nominal
Overall Diameter
Nominal
Copper Weight
kg/Km
Nominal Weight
kg/Km
16(7/24) 1 x 1.5 3 14.4 23
14(7/22) 1 x 2.5 3.6 24 35
12(7/20) 1 x 4 4.2 39 51
10(7/18) 1 x 6 4.7 58 71
8(7/16) 1 x 10 6.1 96 120
6(7/14) 1 x 16 7.2 154 170
4(7/12) 1 x 25 8.4 240 260
2(7/10) 1 x 35 9.5 336 350
1(19/13) 1 x 50 11.3 480 480
2/0(19/11) 1 x 70 12.6 672 680
3/0(19/10) 1 x 95 14.7 912 930
4/0(37/12) 1 x 120 16.2 1152 1160
300MCM(37/11) 1 x 150 18.1 1440 1430
350MCM(37/10) 1 x 185 20.2 1776 1780
500MCM(61/11) 1 x 240 22.9 2304 2360
  1 x 300 24.5 2880 2940
  1 x 400 27.5 3840 3740

PVC H07V-R / H07V-U VOB Cable PACKAGING:
A: Roll of 100 m 
B: Reel of 1500 m. 
C: Reel of 1000 m. 
D: Reel of 500 m. 
E: Multiple Reels of 1000 m. 
Z - Length to the client's requirement.
Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable

PVC H05V-U / H07V-U Nya Cable AVAILABLE COLORS:
Cables (Sizes 0.5mm2 to 6mm2): Black, White, Sky Blue, Blue, Red, Purple, Yellow and Green. 
Cables (Sizes 10mm2 to 25mm2): Black, White, Blue and Red. 
Cables (Sizes 25mm2 to 240mm2): Black. HIGHER SIZES (FROM 750 MCM TO 1.000 MCM), UNDER REQUIREMENT.
Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable

Please contact us for technical support with the right cable selection for your power distribution projects and to discuss your maintenance or project specific requirements. We provide tailored solutions for this cable range which include storage, cutting to length, and 2 days collection as standard.

Any problem and inquiry pls contact with Vivian Yuan.

Cable Vob, H07V-U / H07V-R Electrical Wire Electric Cable

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now