0.6/1 Kv XLPE Insulated Power Cable 4x50 4x70 4x150 4x185 4x240 4x300 AXMK Cable
RATED VOLTAGE: Uo/U = 0,6/1 kV, Um = 1,2 kV
Power cables 1 kV
AXMK-PLUS 4 conductors
APPLICATION:
For fixed installation indoors and outdoors. installable also the ground by plowing.
Maximum conductor temperature:
• Continuous operation at 90 ° C
• in case of a fault (maximum 5 s) 250 ° C
The lowest recommended treatment temperature is -20 ° C
STRUCTURE
Conductor: 16 … 25 mm² circular stranded aluminium, IEC 60228 class 2
35 …300 mm² sector shaped, stranded aluminium, IEC 60228 class 2
Insulation: with UV-resistant XLPE plastic
Twisting Insulated conductors twisted together
Outer sheath: Black UV-resistant PVC/PE
PHASE IDENTIFICATION
Color recognition of wires according to HD 308 S2:
4-wire Yellow-green, brown, black, gray
STANDARDS
SFS 4879 / SFS 5800
HD 603-5D / -5E
IEC 60502-1
EN 50575: 2014 + A1: 2016
EN 13501-6, Category: Eca (CPR fire classification)
IEC 60332-1-2 (self sam.)
PROPERTIES
Specification |
Voltage |
Diameter (mm) |
Weight |
Maximum DC resistance of phase conductor, +20°C (ohm/km) |
AXMK 1x300 |
0,6/1 (1,2) kV |
30 |
1190 |
0.100 |
AXMK 4×16 S |
0,6/1 (1,2) kV |
21 |
380 |
1.910 |
AXMK 5×16 S |
0,6/1 (1,2) kV |
23 |
480 |
1.910 |
AXMK 4×25 S |
0,6/1 (1,2) kV |
25 |
530 |
1.200 |
AXMK 4×35 S |
0,6/1 (1,2) kV |
25 |
650 |
0.868 |
AXMK 4×50 S |
0,6/1 (1,2) kV |
28 |
850 |
0.641 |
AXMK 4×70 S |
0,6/1 (1,2) kV |
32 |
1160 |
0.443 |
AXMK 4×95 S |
0,6/1 (1,2) kV |
35 |
1510 |
0.320 |
AXMK 4×120 S |
0,6/1 (1,2) kV |
40 |
1890 |
0.253 |
AXMK 4×150 S |
0,6/1 (1,2) kV |
44 |
2310 |
0.206 |
AXMK 4×185 S |
0,6/1 (1,2) kV |
49 |
2810 |
0.164 |
AXMK 4×240 S |
0,6/1 (1,2) kV |
55 |
3690 |
0.125 |
AXMK 4×300 S |
0,6/1 (1,2) kV |
59 |
4450 |
0.100 |
*In order to quote you accurate price, kindly tell us your needed cable length quantity. Larger quantity, more discount benefit ready for you!