Aluminum XLPE cable ACSR 3*1/0 AWG Insulated Overhead ABC Cable
Aerial Bundle Conductor (ABC)
Description
Cable Description
Self-supporting system consists of four cores of hard-drawn stranded and compacted aluminium conductors of equal cross-section and insulated with carbon-loaded XLPE to ensure UV protection. All cores strained equally. Supporting-core system consists of three phase cores of hard-drawn stranded compacted aluminium conductors insulated with carbon-loaded XLPE laid up around an aluminium-alloy supporting core insulated with carbon loaded XLPE to ensure UV protection. Additional sub-conductors optional in both self-supporting-core systems.
Installation Information
· Economical
· Flexible
· Safe
· Vandal proof
· Durable
· Aesthetically pleasing
· Adaptable
Technical Data
Rated voltage |
kV |
0.6/1 |
Test voltage |
Veff kV |
4 |
Laying temperature |
°C |
min. -20 |
Operating temperature |
°C |
-30 ~ +80 |
Conductor temperature |
°C |
max. +80 |
Short-circuit temperature |
°C/s |
max. +130 /5 |
Bending radius (min.) |
|
18 × o of cable |
Application
Bundle conductor for overhead distribution network without and with public lighting. (between pole to pole)
Construction:
Conductor Phase |
Stranded All Aluminium conductor (AAC) |
Neutral/Messenger |
Stranded All Alloy Aluminium Conductor (AAAC) |
Insulation |
Extrude of XLPE, capable for continous operation at maximum cable's temperature. |
Properties:
Aluminum XLPE cable ACSR 3*1/0 AWG Insulated Overhead ABC Cable
number of cores x nominal cross section |
max. conductor- resistance |
min. breaking load of conductor strand |
Current rating in the air |
Outer diameter |
Total weight |
mm^2 |
Ohm/km |
kN |
A |
mm |
kg/km |
1x 16 RM |
1,910 |
2,5 |
72 |
80 |
74 |
1x 25 RM |
1,200 |
4,0 |
107 |
90 |
106 |
1x 35 RM |
0,868 |
5,5 |
132 |
105 |
138 |
1x 50 RM |
0,641 |
8,0 |
165 |
118 |
182 |
1x 70 RM |
0,443 |
10,7 |
205 |
130 |
252 |
1x 95 RM |
0,320 |
13,7 |
240 |
154 |
333 |
1x 120 RM |
0,253 |
18,6 |
290 |
170 |
408 |
1x 150 RM |
0,206 |
23,2 |
334 |
190 |
502 |
1x 185 RM |
0,164 |
28,7 |
389 |
210 |
611 |
1x 240 RM |
0,125 |
37,2 |
467 |
240 |
801 |
2x 16 RM |
1,910 |
2,5 |
72 |
156 |
147 |
2x 25 RM |
1,200 |
4,0 |
107 |
180 |
208 |
2x 35 RM |
0,868 |
5,5 |
132 |
200 |
277 |
2x 50 RM |
0,641 |
8,0 |
165 |
235 |
361 |
2x 70 RM |
0,443 |
10,7 |
205 |
254 |
505 |
2x 95 RM |
0,320 |
13,7 |
240 |
303 |
666 |
2x 150 RM |
0,206 |
23,2 |
334 |
380 |
1004 |
4x 16 RM |
1,910 |
2,5 |
72 |
188 |
286 |
4x 25 RM |
1,200 |
4,0 |
107 |
212 |
430 |
4x 35 RM |
0,868 |
5,5 |
132 |
241 |
553 |
4x 50 RM |
0,641 |
8,0 |
165 |
278 |
746 |
4x 70 RM |
0,443 |
10,7 |
205 |
318 |
1009 |
4x 95 RM |
0,320 |
13,7 |
240 |
378 |
1332 |
4x 120 RM |
0,253 |
18,6 |
290 |
544 |
1632 |
4x 50 + 1x 25 RM |
0,641/1,200 |
8,0/4,0 |
165/107 |
319 |
814 |
4x 50 + 1x 35 RM |
0,641/0,868 |
8,5/5,5 |
165/132 |
319 |
845 |
4x 70 + 1x 25 RM |
0,443/1,200 |
10,7/4,0 |
205/107 |
360 |
1105 |
4x 70 + 2x 25 RM |
0,443/1,200 |
10,7/4,0 |
205/107 |
400 |
1217 |
4x 95 + 1x 25 RM |
0,320/1,200 |
13,7/4,0 |
240/107 |
418 |
1438 |
4x 95 + 2x 25 RM |
0,320/1,200 |
13,7/4,0 |
240/107 |
420 |
1544 |
4x120 + 1x 25 RM |
0,253/1,200 |
18,6/4,0 |
290/107 |
590 |
2050 |
other cross-sections on request
Physical Properties |
Cable size |
Insulation Thickness |
Approx Maximum Diameter |
Approx. Net. Weight |
Standard Length |
Phase |
Neutral / Messenger |
Public Lighting |
Phase |
Neutral/Messenger |
Public Lighting |
mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
m |
2x25+25 |
1.4 |
1.4 |
- |
10.0 |
10.0 |
10.0 |
338 |
500 |
2x35+25 |
1.6 |
1.4 |
- |
11.2 |
10.0 |
10.0 |
394 |
500 |
2x50+35 |
1.6 |
1.6 |
- |
12.6 |
11.2 |
11.2 |
526 |
500 |
2x70+50 |
1.8 |
1.6 |
- |
15.4 |
12.6 |
12.6 |
760 |
500 |
2x95+70 |
2.0 |
1.8 |
- |
17.0 |
15.4 |
15.4 |
975 |
500 |
3x25+25 |
1.4 |
1.4 |
- |
10.0 |
10.0 |
10.0 |
452 |
500 |
3x35+25 |
1.6 |
1.4 |
- |
11.2 |
10.0 |
10.0 |
537 |
500 |
3x50+35 |
1.6 |
1.6 |
- |
12.6 |
11.2 |
11.2 |
717 |
500 |
3x70+50 |
1.8 |
1.6 |
- |
15.4 |
12.6 |
12.6 |
1057 |
500 |
3x95+70 |
2.0 |
1.8 |
- |
17.0 |
15.4 |
15.4 |
1360 |
500 |
3x25+25+2x16 |
1.4 |
1.4 |
1.2 |
10.0 |
10.0 |
8.1 |
602 |
500 |
3x35+25+2x16 |
1.6 |
1.4 |
1.2 |
11.2 |
10.0 |
8.1 |
687 |
500 |
3x50+35+2x16 |
1.6 |
1.6 |
1.2 |
12.6 |
11.2 |
8.1 |
867 |
500 |
3x70+50+2x16 |
1.8 |
1.6 |
1.2 |
15.4 |
12.6 |
8.1 |
1207 |
500 |
3x95+70+2x16 |
2.0 |
1.8 |
1.2 |
17.0 |
15.4 |
8.1 |
1510 |
500 |
3x25+25+16 |
1.4 |
1.4 |
1.2 |
10.0 |
10.0 |
8.1 |
527 |
500 |
3x35+25+16 |
1.6 |
1.4 |
1.2 |
11.2 |
10.0 |
8.1 |
612 |
500 |
3x50+35+16 |
1.6 |
1.6 |
1.2 |
12.6 |
11.2 |
8.1 |
792 |
500 |
3x70+50+16 |
1.8 |
1.6 |
1.2 |
15.4 |
12.6 |
8.1 |
1132 |
500 |
3x95+70+16 |
2.0 |
1.8 |
1.2 |
17.0 |
15.4 |
8.1 |
1435 |
500 |
*Further information about rating factor for certain cable arrangement can be found on supplementary technical information
For more information, don't hesitate to contact us on +86-15838290725